dc.contributor.author | Cabello López, Ramón | |
dc.contributor.author | Sánchez García-Vacas, Daniel | |
dc.contributor.author | Llopis, Rodrigo | |
dc.contributor.author | Arauzo Pérez, Ivan | |
dc.contributor.author | Torrella, E. | |
dc.date.accessioned | 2016-09-12T13:42:09Z | |
dc.date.available | 2016-09-12T13:42:09Z | |
dc.date.issued | 2015-07 | |
dc.identifier.citation | CABELLO, R., et al. Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor. International Journal of Refrigeration, 2015, vol. 60, p. 92-105. | ca_CA |
dc.identifier.uri | http://hdl.handle.net/10234/162440 | |
dc.description.abstract | The EU Regulation 517/2014 has recently been approved in a further attempt to curb the effects of Global Warming. As a consequence, the refrigeration sector is moving towards refrigerants with a low Global Warming Potential (GWP100) in accordance with the limit fixed by these regulations (150). In this regard, the old refrigerant R152a attracts renewed interest due to its low GWP (138) and its similarity to R134a. The present work shows the results of using R152a in a vapour compression plant equipped with a hermetic compressor and an IHX designed for R134a. The refrigerant was replaced by a conventional “drop-in” process in order to carry out an energy comparison. The results have revealed an improvement in the COP with R152a up to 13% despite a reduction in the cooling capacity of about 10%. During the test campaign, R134a hermetic compressors have been shown to be capable of operating with R152a. | ca_CA |
dc.description.sponsorShip | The authors acknowledge Jaume I University of Spain, who financed partially the present study through the research project P1⋅B2013-10. | ca_CA |
dc.format.extent | 17 p. | ca_CA |
dc.format.mimetype | application/pdf | ca_CA |
dc.language.iso | eng | ca_CA |
dc.publisher | Elsevier | ca_CA |
dc.relation.isPartOf | International Journal of Refrigeration, 2015, vol. 60, p. 92-105. | ca_CA |
dc.rights | Creative Commons Attribution Non-Commercial No Derivatives License | ca_CA |
dc.rights | Atribución-NoComercial-SinDerivadas 4.0 España | * |
dc.rights.uri | http://creativecommons.org/licenses/by-nc-nd/4.0/ | * |
dc.subject | R152a | ca_CA |
dc.subject | R134a | ca_CA |
dc.subject | F-gas | ca_CA |
dc.subject | Hermetic compressor | ca_CA |
dc.subject | Internal heat exchanger | ca_CA |
dc.subject | GWP | ca_CA |
dc.title | Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor | ca_CA |
dc.title.alternative | Comparaison expérimentale entre R152a et R134a fonctionnant dans une installation frigorifique équipée d'un compresseur hermétique | ca_CA |
dc.type | info:eu-repo/semantics/article | ca_CA |
dc.identifier.doi | http://dx.doi.org/10.1016/j.ijrefrig.2015.06.021 | |
dc.rights.accessRights | info:eu-repo/semantics/openAccess | ca_CA |
dc.relation.publisherVersion | http://www.sciencedirect.com/science/article/pii/S0140700715001905 | ca_CA |
dc.edition | Postprint | ca_CA |
Ficheros en el ítem
Este ítem aparece en la(s) siguiente(s) colección(ones)
-
EMC_Articles [825]