Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor
Ver/ Abrir
Impacto
Scholar |
Otros documentos de la autoría: Cabello López, Ramón; Sánchez García-Vacas, Daniel; Llopis, Rodrigo; Arauzo Pérez, Ivan; Torrella, E.
Metadatos
Mostrar el registro completo del ítemcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadatos
Título
Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressorAutoría
Fecha de publicación
2015-07xmlui.dri2xhtml.METS-1.0.item-edition
PostprintEditor
ElsevierCita bibliográfica
CABELLO, R., et al. Experimental comparison between R152a and R134a working in a refrigeration facility equipped with a hermetic compressor. International Journal of Refrigeration, 2015, vol. 60, p. 92-105.Tipo de documento
info:eu-repo/semantics/articleVersión de la editorial
http://www.sciencedirect.com/science/article/pii/S0140700715001905Palabras clave / Materias
Resumen
The EU Regulation 517/2014 has recently been approved in a further attempt to curb the effects of Global Warming. As a consequence, the refrigeration sector is moving towards refrigerants with a low Global Warming ... [+]
The EU Regulation 517/2014 has recently been approved in a further attempt to curb the effects of Global Warming. As a consequence, the refrigeration sector is moving towards refrigerants with a low Global Warming Potential (GWP100) in accordance with the limit fixed by these regulations (150). In this regard, the old refrigerant R152a attracts renewed interest due to its low GWP (138) and its similarity to R134a.
The present work shows the results of using R152a in a vapour compression plant equipped with a hermetic compressor and an IHX designed for R134a. The refrigerant was replaced by a conventional “drop-in” process in order to carry out an energy comparison. The results have revealed an improvement in the COP with R152a up to 13% despite a reduction in the cooling capacity of about 10%. During the test campaign, R134a hermetic compressors have been shown to be capable of operating with R152a. [-]
Publicado en
International Journal of Refrigeration, 2015, vol. 60, p. 92-105.Derechos de acceso
info:eu-repo/semantics/openAccess
Aparece en las colecciones
- EMC_Articles [828]
El ítem tiene asociados los siguientes ficheros de licencia: