Experimental analysis of R-450A and R-513A as replacements of R-134a and R-507A in a medium temperature commercial refrigeration system
Ver/ Abrir
Impacto
Scholar |
Otros documentos de la autoría: Llopis, Rodrigo; Sánchez García-Vacas, Daniel; Cabello López, Ramón; Catalán-Gil, Jesús; Nebot-Andres, Laura
Metadatos
Mostrar el registro completo del ítemcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadatos
Título
Experimental analysis of R-450A and R-513A as replacements of R-134a and R-507A in a medium temperature commercial refrigeration systemAutoría
Fecha de publicación
2017-09Editor
ElsevierCita bibliográfica
LLOPIS, Rodrigo, et al. Experimental analysis of R-450A and R-513A as replacements of R-134a and R-507A in a medium temperature commercial refrigeration system. International Journal of Refrigeration, 2017, vol. 84, p. 52-66.Tipo de documento
info:eu-repo/semantics/articleVersión de la editorial
http://www.sciencedirect.com/science/article/pii/S0140700717303444Versión
info:eu-repo/semantics/submittedVersionPalabras clave / Materias
Resumen
This work presents the experimental evaluation of R-513A (GWP = 573) and R-450A (GWP = 547) as R-134a (GWP = 1301) drop-in replacements and as R-507A (GWP = 3987) retrofits in a commercial direct expansion refrigeration ... [+]
This work presents the experimental evaluation of R-513A (GWP = 573) and R-450A (GWP = 547) as R-134a (GWP = 1301) drop-in replacements and as R-507A (GWP = 3987) retrofits in a commercial direct expansion refrigeration system for medium temperature applications (2 °C). The evaluation covered 24-hour tests using a single-stage cycle with semi-hermetic compressor, an electronic expansion valve customized for each refrigerant and a commercial vertical cabinet with doors placed inside a climatic chamber. The tests were performed at three water dissipation temperatures (23.3, 32.8 and 43.6 °C). Experimental results indicate that R-513A and R-450A can operate with R-134a plants, with increments in energy consumption between −1.6 to +1.2% for R-513A and from +1.3 to +6.8% for R-450A, whereas in comparison with R-507A, R-513A offered reductions in energy consumption between 4.4 to 8.2% and R-450A between 0 to 3.3%. The paper analyzes the modification of the operating pressures/temperatures and the energy indicators using the four refrigerants. [-]
Proyecto de investigación
Ministerio de Economía y Competitividad, Spain (project ENE2014-53760-R.7)Derechos de acceso
© 2017 Elsevier Ltd and IIR. All rights reserved.
http://rightsstatements.org/vocab/InC/1.0/
info:eu-repo/semantics/openAccess
http://rightsstatements.org/vocab/InC/1.0/
info:eu-repo/semantics/openAccess
Aparece en las colecciones
- EMC_Articles [832]