Protection Strategies for the Connection of Diode Rectifier-Based Wind Power Plants to HVdc Interconnectors
Visualitza/
Impacte
Scholar |
Altres documents de l'autoria: Martínez-Turégano, J.; Vidal-Albalate, Ricardo; Añó-Villalba, Salvador; Bernal-Perez, Soledad; Blasco-Gimenez, Ramon
Metadades
Mostra el registre complet de l'elementcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7034
comunitat-uji-handle3:10234/8619
comunitat-uji-handle4:
INVESTIGACIONMetadades
Títol
Protection Strategies for the Connection of Diode Rectifier-Based Wind Power Plants to HVdc InterconnectorsAutoria
Data de publicació
2020-10-05Editor
Institute of Electrical and Electronics EngineersISSN
2168-6777; 2168-6785Cita bibliogràfica
MARTÍNEZ-TURÉGANO, Jaime, et al. Protection strategies for the connection of diode rectifier-based wind power plants to HVDC interconnectors. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2020, vol. 9, no 6, p. 7018-7031.Tipus de document
info:eu-repo/semantics/articleVersió
info:eu-repo/semantics/acceptedVersionParaules clau / Matèries
Resum
The connection of diode rectifier (DR)-based wind power plants (WPPs) to existing or planned high-voltage dc (HVdc) interconnectors can lead to important savings on cost and system robustness. Since the DR station ... [+]
The connection of diode rectifier (DR)-based wind power plants (WPPs) to existing or planned high-voltage dc (HVdc) interconnectors can lead to important savings on cost and system robustness. Since the DR station usually operates in a bipolar configuration, its connection to symmetric monopoles is particularly challenging. However, there are no published detailed studies on the protection of DR connection WPPs to symmetric monopole interconnectors or even to bipolar interconnectors. This article includes the comparative study of five different protection strategies for such systems, including both solid and resistive DR station grounding and strategies with and without the use of dc-circuit breakers (dcCBs). An analytical study allows for the calculation of fault current during fault onset for both half-bridge and hybrid modular multilevel converter (MMC) stations. Using detailed electromagnetic transient (EMT) simulation studies, the different protection strategies are evaluated in terms of current, voltage, and isolation requirements of each element, as well as the need for dcCBs, fast communication, or larger surge arresters. Moreover, a distance fault detection algorithm is included for the wind turbine converters to distinguish between local ac-grid and dc-cable faults. From the simulation results, it is possible to conclude that DR high-impedance grounding, together with wind turbine distance protection, can be used for the protection of DR-based offshore WPPs connected to symmetric monopole interconnectors without requiring dcCBs. [-]
Publicat a
IEEE Journal of Emerging and Selected Topics in Power Electronics ( Volume: 9, Issue: 6, Dec. 2021)Dades relacionades
https://ieeexplore.ieee.org/document/9212430/figuresDrets d'accés
2168-6777 © 2020 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See https://www.ieee.org/publications/rights/index.html for more information.
http://rightsstatements.org/vocab/InC/1.0/
info:eu-repo/semantics/openAccess
http://rightsstatements.org/vocab/InC/1.0/
info:eu-repo/semantics/openAccess
Apareix a les col.leccions
- ESID_Articles [468]