Energy Evaluation of Multiple Stage Commercial Refrigeration Architectures Adapted to F-Gas Regulation
![Thumbnail](/xmlui/bitstream/handle/10234/176895/Catalan_2018_Energy.pdf.jpg?sequence=5&isAllowed=y)
View/ Open
Impact
![Google Scholar](/xmlui/themes/Mirage2/images/uji/logo_google.png)
![Microsoft Academico](/xmlui/themes/Mirage2/images/uji/logo_microsoft.png)
Metadata
Show full item recordcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadata
Title
Energy Evaluation of Multiple Stage Commercial Refrigeration Architectures Adapted to F-Gas RegulationAuthor (s)
Date
2018-07-23Publisher
MDPIBibliographic citation
CATALÁN-GIL, Jesús; SÁNCHEZ GARCÍA-VACAS, Daniel; LLOPIS DOMÉNECH, Rodrigo; NEBOT ANDRÉS, Laura; CABELLO LÓPEZ, Ramón (2018). Energy Evaluation of Multiple Stage Commercial Refrigeration Architectures Adapted to F-Gas Regulation. Energies, 11(7), 1915Type
info:eu-repo/semantics/articlePublisher version
https://www.mdpi.com/1996-1073/11/7/1915Version
info:eu-repo/semantics/publishedVersionSubject
Abstract
This work analyses different refrigeration architectures for commercial refrigeration providing
service to medium and low temperature simultaneously: HFC/R744 cascade, R744 transcritical booster,
R744 transcritical ... [+]
This work analyses different refrigeration architectures for commercial refrigeration providing
service to medium and low temperature simultaneously: HFC/R744 cascade, R744 transcritical booster,
R744 transcritical booster with parallel compression, R744 transcritical booster with gas ejectors,
R513A cascade/R744 subcritical booster, and R513A cascade/R744 subcritical booster with parallel
compression. The models were developed using compressor manufacturers’ data and real restrictions of
each system component.
Limitations and operating range of each component and architecture were
analysed for environment temperatures from 0 to 40
◦
C considering thermal loads and environment
temperature profiles for warm climates. For booster systems, cascade with subcritical booster with
parallel compression provide highest coefficient of performance (COP) for temperatures below 12
◦
C
and above 30
◦
C with COP increases compared basic booster up to 60.6%, whereas for transcritical
boosters, architecture with gas ejectors obtains the highest COP with COP increases compared
to the basic booster up to 29.5%. In annual energy terms, differences among improved booster
systems are below 8% in the locations analysed. In Total Equivalent Warming Impact (TEWI) terms,
booster architectures get the lowest values with small differences between improved boosters. [-]
Is part of
Energies (2018), 11(7)Rights
info:eu-repo/semantics/openAccess