Experimental assessment of R134a and its lower GWP alternative R513A
View/ Open
Impact
Scholar |
Other documents of the author: Mota-Babiloni, Adrián; Makhnatch, Pavel; Khodabandeh, Rahmatollah; Navarro-Esbrí, Joaquín
Metadata
Show full item recordcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadata
Title
Experimental assessment of R134a and its lower GWP alternative R513AAuthor (s)
Date
2017-02Publisher
ElsevierBibliographic citation
MOTA-BABILONI, Adrián, et al. Experimental assessment of R134a and its lower GWP alternative R513A. International Journal of Refrigeration, 2017, vol. 74, p. 680-686.Type
info:eu-repo/semantics/articlePublisher version
http://www.sciencedirect.com/science/article/pii/S0140700716304066Subject
Abstract
Lower GWP refrigerants are essential to mitigate the impact of refrigeration systems on climate change. HFO/HFC mixtures are currently considered to replace HFCs in refrigeration and air conditioning systems. The aim ... [+]
Lower GWP refrigerants are essential to mitigate the impact of refrigeration systems on climate change. HFO/HFC mixtures are currently considered to replace HFCs in refrigeration and air conditioning systems. The aim of this paper is to present the main operating and performance differences between R513A (GWP of 573) and R134a (GWP of 1300), the most used refrigerants for medium evaporation temperature refrigeration systems and mobile air conditioners. To perform the experimental comparison, 36 tests are carried out with each refrigerant at evaporating temperatures between −15 and 12.5°C and condensing temperatures between 25 and 35°C. The conclusion of the experimental comparison is that R513A can substitute R134a with only a thermostatic expansion valve adjustment, achieving better performance and higher cooling capacity. The discharge temperature of R513A is always lower than that of R134a. [-]
Is part of
International Journal of Refrigeration, 2017, vol. 74Rights
© 2016 Elsevier Ltd and IIR. All rights reserved.
http://rightsstatements.org/vocab/InC/1.0/
info:eu-repo/semantics/openAccess
http://rightsstatements.org/vocab/InC/1.0/
info:eu-repo/semantics/openAccess
This item appears in the folowing collection(s)
- EMC_Articles [825]