Títol
Experimental evaluation of HCFO-1233zd-E as HFC-245fa replacement in an Organic Rankine Cycle system for low temperature heat sourcesData de publicació
2016-04-05Editor
ElsevierISSN
1359-4311Cita bibliogràfica
MOLÉS, Francisco, et al. Experimental evaluation of HCFO-1233zd-E as HFC-245fa replacement in an Organic Rankine Cycle system for low temperature heat sources. Applied Thermal Engineering, 2016, vol. 98, p. 954-961Tipus de document
info:eu-repo/semantics/articleVersió de l'editorial
http://www.sciencedirect.com/science/article/pii/S135943111600065XVersió
info:eu-repo/semantics/submittedVersionParaules clau / Matèries
Resum
In this work an experimental evaluation of the working fluid HCFO-1233zd-E as HFC-245fa replacement in ORC systems for low temperature heat sources has been conducted. A fully monitored ORC module has been used to ... [+]
In this work an experimental evaluation of the working fluid HCFO-1233zd-E as HFC-245fa replacement in ORC systems for low temperature heat sources has been conducted. A fully monitored ORC module has been used to test both working fluids at different operating conditions. Due to the different densities of the working fluids, the mass flow rate for HCFO-1233zd-E is approximately 20% lower than for HFC-245fa. This causes thermal and electrical powers to be lower for HCFO-1233zd-E than for HFC-245fa. However, net electrical efficiency is similar for both working fluids, ranging from 5% to 9.7% in the tested operating conditions. Regarding the expander performance, various performance indicators are addressed. The expander isentropic performance has a maximum value of 75%, with higher values for HCFO-1233zd-E than for HFC-245fa. The overall efficiency of the expander, similar for both working fluids, ranges from 44% to 57% in the experimental test range. [-]