Mostrar el registro sencillo del ítem

dc.contributor.authorLlopis, Rodrigo
dc.contributor.authorSanz Kock, Carlos
dc.contributor.authorCabello López, Ramón
dc.contributor.authorSánchez García-Vacas, Daniel
dc.contributor.authorTorrella Alcaraz, Enrique
dc.date.accessioned2016-05-06T10:58:17Z
dc.date.available2016-05-06T10:58:17Z
dc.date.issued2015-04-05
dc.identifier.citationLLOPIS DOMÉNECH, Rodrigo; SANZ KOCK, Carlos; CABELLO LÓPEZ, Ramón; SÁNCHEZ GARCÍA-VACAS, Daniel; TORRELA ALCARAZ, Enrique. Experimental evaluation of an Internal Heat Exchanger in a CO2 subcritical refrigeration cycle with gas-cooler. Applied Thermal Engineering (2015), v. 80, n. 5, pp 31-41ca_CA
dc.identifier.urihttp://hdl.handle.net/10234/159362
dc.description.abstractWe present the experimental evaluation of an internal heat exchanger or suction-line/liquid-line heat exchanger in a CO2 subcritical refrigeration plant with gas-cooler. The plant, driven by a 1.5kW CO2 semi hermetic compressor, uses brazed plate heat exchangers as condenser, evaporator and internal heat exchanger, an air finned tube gas-cooler and an electronic expansion valves. The evaluation (77 steady- states) covers evaporating temperatures from -40 to -25 oC and condensing temperatures from -15 to 0 oC, always at the nominal speed of the compressor. Here, the effect of the internal heat exchanger on the main energy parameters is analysed, i.e., cooling capacity, COP and heat rejection at gas-cooler and condenser. Also, the effect of the internal heat exchanger in a cascade cycle is analysed theoretically. It has been concluded that the internal heat exchanger does not improve the performance of the subcritical cycle, but it could improve the energy performance if it is used inside a cascade refrigeration system.ca_CA
dc.description.sponsorShipThe authors gratefully acknowledge Jaume I University of Spain, who financed the present study through the research project P1·B2013-10.ca_CA
dc.format.extent24 p.ca_CA
dc.format.mimetypeapplication/pdfca_CA
dc.language.isoengca_CA
dc.publisherElsevierca_CA
dc.relation.isPartOfApplied Thermal Engineering (2015), v. 80, n. 5ca_CA
dc.rights.urihttp://rightsstatements.org/vocab/CNE/1.0/*
dc.subjectCO2ca_CA
dc.subjectSubcriticalca_CA
dc.subjectInternal heat exchangerca_CA
dc.subjectCascadeca_CA
dc.subjectExperimentalca_CA
dc.titleExperimental evaluation of an Internal Heat Exchanger in a CO2 subcritical refrigeration cycle with gas-coolerca_CA
dc.typeinfo:eu-repo/semantics/articleca_CA
dc.identifier.doihttp://dx.doi.org/10.1016/j.applthermaleng.2015.01.040
dc.rights.accessRightsinfo:eu-repo/semantics/openAccessca_CA
dc.relation.publisherVersionhttp://www.sciencedirect.com/science/article/pii/S1359431115000459ca_CA
dc.editionPostprintca_CA


Ficheros en el ítem

Thumbnail

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem