Experimental evaluation of an Internal Heat Exchanger in a CO2 subcritical refrigeration cycle with gas-cooler
Ver/ Abrir
Impacto
Scholar |
Otros documentos de la autoría: Llopis, Rodrigo; Sanz Kock, Carlos; Cabello López, Ramón; Sánchez García-Vacas, Daniel; Torrella Alcaraz, Enrique
Metadatos
Mostrar el registro completo del ítemcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadatos
Título
Experimental evaluation of an Internal Heat Exchanger in a CO2 subcritical refrigeration cycle with gas-coolerAutoría
Fecha de publicación
2015-04-05xmlui.dri2xhtml.METS-1.0.item-edition
PostprintEditor
ElsevierCita bibliográfica
LLOPIS DOMÉNECH, Rodrigo; SANZ KOCK, Carlos; CABELLO LÓPEZ, Ramón; SÁNCHEZ GARCÍA-VACAS, Daniel; TORRELA ALCARAZ, Enrique. Experimental evaluation of an Internal Heat Exchanger in a CO2 subcritical refrigeration cycle with gas-cooler. Applied Thermal Engineering (2015), v. 80, n. 5, pp 31-41Tipo de documento
info:eu-repo/semantics/articleVersión de la editorial
http://www.sciencedirect.com/science/article/pii/S1359431115000459Palabras clave / Materias
Resumen
We present the experimental evaluation of an internal heat exchanger or suction-line/liquid-line heat exchanger in a CO2 subcritical refrigeration plant with gas-cooler. The plant, driven by a 1.5kW CO2 semi hermetic ... [+]
We present the experimental evaluation of an internal heat exchanger or suction-line/liquid-line heat exchanger in a CO2 subcritical refrigeration plant with gas-cooler. The plant, driven by a 1.5kW CO2 semi hermetic compressor, uses brazed plate heat exchangers as condenser, evaporator and internal heat exchanger, an air finned tube gas-cooler and an electronic expansion valves. The evaluation (77 steady- states) covers evaporating temperatures from -40 to -25 oC and condensing temperatures from -15 to 0 oC, always at the nominal speed of the compressor. Here, the effect of the internal heat exchanger on the main energy parameters is analysed, i.e., cooling capacity, COP and heat rejection at gas-cooler and condenser. Also, the effect of the internal heat exchanger in a cascade cycle is analysed theoretically. It has been concluded that the internal heat exchanger does not improve the performance of the subcritical cycle, but it could improve the energy performance if it is used inside a cascade refrigeration system. [-]
Publicado en
Applied Thermal Engineering (2015), v. 80, n. 5Derechos de acceso
http://rightsstatements.org/vocab/CNE/1.0/
info:eu-repo/semantics/openAccess
info:eu-repo/semantics/openAccess
Aparece en las colecciones
- EMC_Articles [825]