dc.identifier.citationAl-Sayyab, Ali Khalid Shaker; Mota Babiloni, Adrián; Barragán Cervera, Angel; Navarro Esbrí, Joaquín. Experimental drop-in comparison of R516A and R134A for water-to-water refrigeration applications. En: XI Congreso Ibérico y IX Congreso Iberoamericano de Ciencias y Técnicas del Frío Cytef2022. Avances en Ciencias y Técnicas del Frío - 11. Cartagena: Universidad Politécnica de Cartagena, 2022. Pp. 250-255. ISBN: 978-84-17853-55-6ca_CA
dc.identifier.isbn9788417853556
dc.identifier.urihttp://hdl.handle.net/10234/206545
dc.descriptionPonència presentada al XI Congreso Ibérico y IX Congreso Iberoamericano de Ciencias y Técnicas del Frío Cytef2022. Cartagena (Spain), 17-19 abril, 2022.ca_CA
dc.description.abstractR134a is still one of the most used hydrofluorocarbons (HFCs) in refrigeration and air conditioning applications. However, it should be phased out in the coming years because of its high global warming potential (GWP). The refrigeration sector needs to find as soon as possible technically suitable alternative refrigerants. R516A is a promising azeotropic mixture at medium-low temperatures. The operational and energetic performance of the lower GWP refrigerant R516A is analysed as a drop-in replacement to R134a. Experimental measurements are taken from in vapour compression test rig at several steady-state refrigeration conditions. The evaporating temperature is -5 ºC, -10 ºC and -15 ºC, and is combined with 32.5 ºC condensing temperature, considering the effect of the internal heat exchanger (IHX) effectiveness. R516A presents a good performance in terms of refrigerating effect and cooling capacity. R516A coefficient of performance (COP) is higher than R134a at the evaporating temperature of 15ºC.ca_CA
dc.format.extent5 p.ca_CA
dc.format.mimetypeapplication/pdfca_CA
dc.language.isoengca_CA
dc.publisherUniversidad Politécnica de Cartagena. Ediciones UPCTca_CA
dc.rights©2022, los editores. ©2022, UNIVERSIDAD POLITÉCNICA DE CARTAGENA.ca_CA
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/ca_CA
dc.subjectCYTEFca_CA
dc.subjectcoolingca_CA
dc.subjectvapour compression systemca_CA
dc.subjectlow global warming potential (GWP)ca_CA
dc.subjectR516Aca_CA
dc.titleExperimental drop-in comparison of R516A for water-to-water refrigeration applicationsca_CA
dc.typeinfo:eu-repo/semantics/conferenceObjectca_CA
dc.rights.accessRightsinfo:eu-repo/semantics/openAccessca_CA
dc.type.versioninfo:eu-repo/semantics/publishedVersionca_CA
dc.subject.ods9. Industria, innovacion e infraestructuraca_CA


Ficheros en el ítem

Thumbnail

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem

©2022, los editores.
©2022, UNIVERSIDAD POLITÉCNICA DE CARTAGENA.
Excepto si se señala otra cosa, la licencia del ítem se describe como: ©2022, los editores. ©2022, UNIVERSIDAD POLITÉCNICA DE CARTAGENA.