Mostrar el registro sencillo del ítem

dc.contributor.authorMota-Babiloni, Adrián
dc.contributor.authorNavarro-Esbrí, Joaquín
dc.contributor.authorBarragán Cervera, Angel
dc.contributor.authorMolés, Francisco
dc.contributor.authorPeris, Bernardo
dc.date.accessioned2021-07-12T10:25:49Z
dc.date.available2021-07-12T10:25:49Z
dc.date.issued2014-12-20
dc.identifier.citationMOTA-BABILONI, Adrián, et al. Experimental study of an R1234ze (E)/R134a mixture (R450A) as R134a replacement. International Journal of Refrigeration, 2015, vol. 51, p. 52-58.ca_CA
dc.identifier.issn0140-7007
dc.identifier.urihttp://hdl.handle.net/10234/193823
dc.description.abstractThis work presents an experimental analysis of a non-flammable R1234ze(E)/R134a mixture (R450A) as R134a drop-in replacement. While R134a has a high GWP value (1430), the R450A GWP is only 547. The experimental tests are carried out in a vapour compression plant equipped with a variable-speed compressor. The replacement suitability has been studied combining different operating conditions: evaporation temperature, condensation temperature and the use of an internal heat exchanger (IHX). The drop-in cooling capacity of R450A compared with R134a is 6% lower as average. R450A COP is even higher to those resulting with R134a (approximately 1%). The discharge temperature of R450A is lower than that of R134a, 2K as average. The IHX has a similar positive influence on the energy performance of both fluids. In conclusion, R450A can be considered as a good candidate to replace R134a.ca_CA
dc.format.extent19 p.ca_CA
dc.format.mimetypeapplication/pdfca_CA
dc.language.isoengca_CA
dc.publisherElsevierca_CA
dc.relation.isPartOfInternational Journal of Refrigeration Volume 51, March 2015, Pages 52-58ca_CA
dc.rights0140-7007/©2014 Elsevier Ltd and IIR. All rights reserved.ca_CA
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/ca_CA
dc.subjectrefrigerationca_CA
dc.subjectR450Aca_CA
dc.subjectR134aca_CA
dc.subjectmixtureca_CA
dc.subjectenergy efficiencyca_CA
dc.subjectdrop-inca_CA
dc.subjectréfrigérationca_CA
dc.subjectmélange de frigorigènesca_CA
dc.subjectefficacité énergétiqueca_CA
dc.subjectfrigorigène de remplacement immédiatca_CA
dc.titleExperimental study of an R1234ze(E)/R134a mixture (R450A) as R134a replacementca_CA
dc.title.alternativeEtude expérimentale d'un mélange de R1234ze et de R134a (R450A) comme remplacement du R134aca_CA
dc.typeinfo:eu-repo/semantics/articleca_CA
dc.identifier.doihttps://doi.org/10.1016/j.ijrefrig.2014.12.010
dc.rights.accessRightsinfo:eu-repo/semantics/openAccessca_CA
dc.relation.publisherVersionhttps://www.sciencedirect.com/journal/international-journal-of-refrigerationca_CA
dc.type.versioninfo:eu-repo/semantics/acceptedVersionca_CA


Ficheros en el ítem

Thumbnail

Este ítem aparece en la(s) siguiente(s) colección(ones)

Mostrar el registro sencillo del ítem

0140-7007/©2014 Elsevier Ltd and IIR. All rights reserved.
Excepto si se señala otra cosa, la licencia del ítem se describe como: 0140-7007/©2014 Elsevier Ltd and IIR. All rights reserved.