dc.date.issued2021-01-20
dc.identifier.citationCABELLO, Ramón, et al. Energy evaluation of a Low Temperature commercial refrigeration plant working with the new low-GWP blend R468A as drop-in of R404A. International Journal of Refrigeration, 2021.ca_CA
dc.identifier.issn0140-7007
dc.identifier.urihttp://hdl.handle.net/10234/192678
dc.description.abstractThis work analyses experimentally the energy behaviour of a centralized commercial refrigeration plant designed to be used with R404A (GWP100=3,943) at low temperatures, when it is replaced with the new low-GWP refrigerant blend R468A (GPW100=148). The tests have been done at a selected product temperature of -20°C, Class III indoor conditions according to ISO 23953-2:2015 and 20, 30 and 40°C of heat sink temperature. The product has been kept at the requested temperature in whichever conditions tested. Respect to R404A, running with R468A presents an increase in compressor discharge temperature, greater compressión operation time, and a reduction in compressor electric comssumption that yields in a very similar total energy consumption of the refrigeration plant. So it has been proved that, from an operational point of view, R468A can be a R404A drop in replacement fluid. Also, it has been measured energy savings when an internal heat exchanger is placed.ca_CA
dc.format.extent28 p.ca_CA
dc.format.mimetypeapplication/pdfca_CA
dc.language.isoengca_CA
dc.publisherElsevierca_CA
dc.relation.isPartOfInternational Journal of Refrigeration Available online 20 January 2021ca_CA
dc.rights© 2021 Published by Elsevier Ltd.ca_CA
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 Internacional*
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/*
dc.subjectR468Aca_CA
dc.subjectR404Aca_CA
dc.subjectIHXdrop-inca_CA
dc.subjectF-Gasca_CA
dc.subjectcommercial refrigerationca_CA
dc.subjectenergy analysisca_CA
dc.titleEnergy evaluation of a Low Temperature commercial refrigeration plant working with the new low-GWP blend R468A as drop-in of R404Aca_CA
dc.typeinfo:eu-repo/semantics/articleca_CA
dc.identifier.doihttps://doi.org/10.1016/j.ijrefrig.2021.01.012
dc.rights.accessRightsinfo:eu-repo/semantics/openAccessca_CA
dc.relation.publisherVersionhttps://www.sciencedirect.com/science/article/pii/S0140700721000323#!ca_CA
dc.type.versioninfo:eu-repo/semantics/acceptedVersionca_CA
project.funder.nameMinisterio de Ciencia y Tecnologíaca_CA
project.funder.nameUniversitat Jaume Ica_CA
oaire.awardNumberRTI2018-093501-B-C21ca_CA
oaire.awardNumberUJI-B2019-56ca_CA
dc.subject.ods03