dc.identifier.citationAL-SAYYAB, Ali Khalid Shaker; MOTA-BABILONI, Adrián; NAVARRO-ESBRÍ, Joaquín. Novel compound waste heat-solar driven ejector-compression heat pump for simultaneous cooling and heating using environmentally friendly refrigerants. Energy Conversion and Management, 228: 113703ca_CA
dc.identifier.issn0196-8904
dc.identifier.urihttp://hdl.handle.net/10234/191578
dc.description.abstractThis work investigates the theoretical performance of a novel compound waste heat-solar driven ejector-solar assisted heat pump for simultaneous heating and cooling purposes. The system utilizes waste heat from three different sources, PV/T (photovoltaic thermal) with flat plate collector, milk pasteurization process, and condenser exchange heat. Real weather data is employed to determine the hourly performance of the system in three European cities, Valencia (Spain), Berlin (Germany), and Stockholm (Sweden) representing warm, middle and cold climates, respectively. Moreover, R450A and R513A alternative refrigerants are compared to the greenhouse gas R134a. The results show that the proposed system improves cooling COP by 7% using R450A in comparison with a conventional R134a vapor compression system. Furthermore, the utilization of waste heat recovery enhances the system COP from 3.7 to 4 in the absence of solar intensity. On the other hand, the results of the heating mode show that the system with PV/T and using R450A has a COP increase over the adopted solar time, ranging from 2 to 5% in Valencia; 2 to 2.5% in Berlin, and1 to 1.5% in Stockholm. However, R513A shows a COP reduction of about 5% in comparison to R134a. Regarding the heating mode with waste heat utilization from milk pasteurization, the system based on R450A results in the highest system COP, increasing COP up to 75% compared to the R134a baseline scenario. Overall, the proposed R450A systems show the highest equivalent carbon dioxide emission reduction and, therefore, it is recommended from an environmental point of view.ca_CA
dc.format.extent15 p.ca_CA
dc.format.mimetypeapplication/pdfca_CA
dc.language.isoengca_CA
dc.publisherElsevierca_CA
dc.relation.isPartOfEnergy Conversion and Management, 228: 113703
dc.rights© 2020 Elsevier Ltd. All rights reserved.
dc.rightsAttribution-NonCommercial-NoDerivatives 4.0 Internacional
dc.rights.urihttp://creativecommons.org/licenses/by-nc-nd/4.0/
dc.subjectwaste heat recoveryca_CA
dc.subjectPV/Tca_CA
dc.subjectlow global warming potential (GWP)ca_CA
dc.subjectrefrigerantsca_CA
dc.subjectsolar ejectorca_CA
dc.subjectvapor compressionca_CA
dc.titleNovel compound waste heat-solar driven ejector-compression heat pump for simultaneous cooling and heating using environmentally friendly refrigerantsca_CA
dc.typeinfo:eu-repo/semantics/articleca_CA
dc.identifier.doihttps://doi.org/10.1016/j.enconman.2020.113703
dc.rights.accessRightsinfo:eu-repo/semantics/openAccessca_CA
dc.type.versioninfo:eu-repo/semantics/acceptedVersionca_CA


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record

© 2020 Elsevier Ltd. All rights reserved.
Except where otherwise noted, this item's license is described as © 2020 Elsevier Ltd. All rights reserved.