Mostrar el registro sencillo del ítem

dc.contributor.authorLlopis, Rodrigo
dc.contributor.authorSánchez García-Vacas, Daniel
dc.contributor.authorCabello López, Ramón
dc.contributor.authorCatalán-Gil, Jesús
dc.contributor.authorNebot-Andres, Laura
dc.date.accessioned2018-05-30T11:00:20Z
dc.date.available2018-05-30T11:00:20Z
dc.date.issued2018-02-06
dc.identifier.citationLLOPIS, Rodrigo, et al. Conversion of a Direct to an Indirect Refrigeration System at Medium Temperature Using R-134a and R-507A: An Energy Impact Analysis. Applied Sciences, 2018, vol. 8, no 2, p. 247ca_CA
dc.identifier.issn2076-3417
dc.identifier.urihttp://hdl.handle.net/10234/174871
dc.description.abstractThis work presents the experimental evaluation of energy consumption and refrigerant charge reduction when a commercial direct expansion refrigeration system is converted into an indirect system. The evaluation (with R-134a and R-507A) used a commercial cabinet with doors for medium temperature and a single-stage refrigeration cycle using a semi-hermetic compressor and electronic expansion valve; 24-h energy consumption tests were performed at laboratory conditions for each refrigerant and configuration at three heat rejection levels (23.3, 32.8 and 43.6 °C), maintaining an average product temperature inside the cabinet of 2 °C. The work analyses the impact of the conversion on temperature and pressure indicators, as well as, in the energy performance of each element. For R-134a the refrigerant charge was reduced in a 42.9%, but the energy consumption rose by 22.0%–22.8%; for R-507A the charge reduction was of 32.8% with an increase in energy consumption of between 27.7% and 38.7%.ca_CA
dc.format.extent17 p.ca_CA
dc.format.mimetypeapplication/pdfca_CA
dc.language.isoengca_CA
dc.publisherMDPIca_CA
dc.relation.isPartOfApplied Sciences, 2018, vol. 8, no 2ca_CA
dc.rightsAtribución 4.0 Internacional*
dc.rights.urihttp://creativecommons.org/licenses/by-sa/4.0/*
dc.subjectR-134aca_CA
dc.subjectR-507Aca_CA
dc.subjectindirect systemca_CA
dc.subjectcommercial refrigerationca_CA
dc.subjectenergy analysisca_CA
dc.titleConversion of a Direct to an Indirect Refrigeration System at Medium Temperature Using R-134a and R-507A: An Energy Impact Analysisca_CA
dc.typeinfo:eu-repo/semantics/articleca_CA
dc.identifier.doihttp://dx.doi.org/10.3390/app8020247
dc.relation.projectIDMinisterio de Economia y Competitividad of Spain: ENE2014-53760-R.7, FPI BES-2015-073612; Jaume I University of Spain: P11B2015-66; Generalitat Valenciana of Spain: ACIF/2017/194ca_CA
dc.rights.accessRightsinfo:eu-repo/semantics/openAccessca_CA
dc.relation.publisherVersionhttp://www.mdpi.com/2076-3417/8/2/247/htmlca_CA