Mostrar el registro sencillo del ítem

dc.contributor.authorSánchez García-Vacas, Daniel
dc.contributor.authorCabello López, Ramón
dc.contributor.authorLlopis, Rodrigo
dc.contributor.authorCatalán-Gil, Jesús
dc.contributor.authorNebot-Andres, Laura
dc.date.accessioned2018-05-21T10:39:03Z
dc.date.available2018-05-21T10:39:03Z
dc.date.issued2018-07-05
dc.identifier.citationSÁNCHEZ, D., et al. Energy assessment of an R134a refrigeration plant upgraded to an indirect system using R152a and R1234ze (E) as refrigerants. Applied Thermal Engineering, 2018, vol. 139, p. 121-134ca_CA
dc.identifier.issn1359-4311
dc.identifier.issn1873-5606
dc.identifier.urihttp://hdl.handle.net/10234/174760
dc.description.abstractIn this work the experimental results obtained from a direct expansion refrigerating plant converted into an indirect plant, are presented and discussed in terms of energy consumption for a commercial refrigerating unit plugged to a medium temperature cabinet. Refrigerants used in the analysis are R134a for direct system, and R134a, R152a and R1234ze(E) for indirect system. The evaluation has been performed at laboratory conditions using three different heat rejection levels: 43.6, 32.8 and 23.3 °C keeping constant the environmental conditions in the cabinet (25 °C; 55%). From the experimental tests performed during 24 h, it has been demonstrated that the adoption of an indirect configuration results in an increment of the total energy consumption of the refrigerating plant regardless the refrigerant adopted. The average increment registered was 21.8% for R134a, 18.7% for R152a and finally 27.2% for R1234ze(E). The adoption of an indirect system also reduces the refrigerant mass charge of the facility up to 62% depending on the refrigerant used.ca_CA
dc.format.mimetypeapplication/pdfca_CA
dc.language.isoengca_CA
dc.publisherElsevierca_CA
dc.relation.isPartOfApplied Thermal Engineering, 2018, vol. 139ca_CA
dc.rightsCopyright © Elsevier B.V.ca_CA
dc.rights.urihttp://rightsstatements.org/vocab/InC/1.0/*
dc.subjectcommercial refrigerationca_CA
dc.subjectindirect systemca_CA
dc.subjectR134aca_CA
dc.subjectR152aca_CA
dc.subjectR1234ze(E)ca_CA
dc.subjectenergy consumptionca_CA
dc.subjectrefrigerant charge reductionca_CA
dc.titleEnergy assessment of an R134a refrigeration plant upgraded to an indirect system using R152a and R1234ze(E) as refrigerantsca_CA
dc.typeinfo:eu-repo/semantics/articleca_CA
dc.identifier.doihttps://doi.org/10.1016/j.applthermaleng.2018.04.114
dc.rights.accessRightsinfo:eu-repo/semantics/openAccessca_CA
dc.relation.publisherVersionhttps://www.sciencedirect.com/science/article/pii/S1359431117380316ca_CA
dc.contributor.funderThe authors would like to acknowledge the financial support of Universitat Jaume I of Castellón, Spain through the research project P11B2015-66, and the Spanish Ministry of Economy and Competitiveness through the research project ENE2014-53760-R.ca_CA
dc.type.versioninfo:eu-repo/semantics/submittedVersionca_CA