Reduced-Order Models of Squirrel-Cage Induction Generators for Fixed-Speed Wind Turbines under Unbalanced Grid Conditions
Visualitza/
Impacte
Scholar |
Altres documents de l'autoria: Rolán Blanco, Alejandro; Córcoles López, Felipe; Bogarra, Santiago; Monjo, Lluís; Pedra Durán, Joaquín
Metadades
Mostra el registre complet de l'elementcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7034
comunitat-uji-handle3:10234/8619
comunitat-uji-handle4:
INVESTIGACIONMetadades
Títol
Reduced-Order Models of Squirrel-Cage Induction Generators for Fixed-Speed Wind Turbines under Unbalanced Grid ConditionsAutoria
Data de publicació
2016-06Editor
Institute of Electrical and Electronics Engineers (IEEE)Cita bibliogràfica
ROLDÁN BLANCO, Alejandro; CÓRCOLES LÓPEZ, Felipe; BOGARRA, Santiago; MONJO, Lluís; PEDRA DURÁN, Joaquín. Reduced-Order Models of Squirrel-Cage Induction Generators for Fixed-Speed Wind Turbines under Unbalanced Grid Conditions. IEEE Transactions on Energy Conversion (2016), v. 31, n. 2, pp. 566-577Tipus de document
info:eu-repo/semantics/articleVersió de l'editorial
http://ieeexplore.ieee.org/stamp/stamp.jsp?arnumber=7359165Paraules clau / Matèries
Resum
This paper develops a study of reduced-order
models for squirrel-cage induction generators (SCIG) used in
fixed-speed wind turbines (WTs). The squirrel-cage of these
generators must be modeled with a double-cage ... [+]
This paper develops a study of reduced-order
models for squirrel-cage induction generators (SCIG) used in
fixed-speed wind turbines (WTs). The squirrel-cage of these
generators must be modeled with a double-cage for accuracy
purposes. These proposed reduced-order models are valid for
unbalanced grid conditions (unsymmetrical faults), which
require flux and current decomposition into positive- and
negative-sequences. Three reduced-order models are obtained:
R2 model, where the derivative of the positive- and negativesequences
of the stator fluxes are neglected (the usual approach
in the literature); R1 model, where the derivative of the negativesequence
of the rotor fluxes are also neglected (proposed model);
and R0 model, where all the stator and rotor fluxes are neglected
(steady-state electrical model). The analytical models are
validated with simulations carried out in MATLABTM and with
experimental tests. The results show that R1 model (proposed
model) shows a good performance (similar to the full-order
model) under unbalanced conditions. [-]
Publicat a
IEEE Transactions on Energy Conversion (2016), v. 31, n. 2Drets d'accés
http://rightsstatements.org/vocab/CNE/1.0/
info:eu-repo/semantics/openAccess
info:eu-repo/semantics/openAccess
Apareix a les col.leccions
- ESID_Articles [478]