This paper analyzes the behavior of a modular multilevel
converter-high-voltage direct-current (MMC-HVDC)-connected
offshore wind power plant (WPP) during dc faults. For
that purpose, detailed models of the dc ... [+]
This paper analyzes the behavior of a modular multilevel
converter-high-voltage direct-current (MMC-HVDC)-connected
offshore wind power plant (WPP) during dc faults. For
that purpose, detailed models of the dc cable, MMC stations, and
transformers have been used in order to obtain reliable results.
The influence of the WPP control method in the short-circuit behavior
of the HVDC link has also been studied. Results show that
the dynamics of the WPP contribution to pole-to-ground faults
are slightly slower than those of the wind turbines current control
loops. Therefore, the wind turbine front-end converters can be
used to reduce the peak and average value of the fault current
in such a system. Moreover, it has been found that ferroresonant
oscillations can appear in the offshore ac grid when the WPP
delivers constant power during faults. [-]
Derechos de acceso
"This work has been submitted to the IEEE for possible publication. Copyright may be transferred without notice, after which this version may no longer be accessible"
©2015 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other users, including reprinting/ republishing this material for advertising or promotional purposes, creating new collective works for resale or redistribution to servers or lists, or reuse of any copyrighted components of this work in other works."