Título
Comprehensive experimental evaluation of R1234yf-based low GWP working fluids for refrigeration and heat pumpsAutoría
Fecha de publicación
2022-03-17Editor
ElsevierCita bibliográfica
AL-SAYYAB, Ali Khalid Shaker, et al. Comprehensive experimental evaluation of R1234yf-based low GWP working fluids for refrigeration and heat pumps. Energy Conversion and Management, 2022, vol. 258, p. 115378.Tipo de documento
info:eu-repo/semantics/articleVersión
info:eu-repo/semantics/publishedVersionPalabras clave / Materias
Resumen
This work presents an experimental comparison for low GWP refrigerants used in vapour compression cooling and heating systems. The study compares three lower global warming potential (GWP) refrigerants (R513A, R516A, ... [+]
This work presents an experimental comparison for low GWP refrigerants used in vapour compression cooling and heating systems. The study compares three lower global warming potential (GWP) refrigerants (R513A, R516A, and R1234yf) as drop-in refrigerants to replace the hydrofluorocarbon (HFC) R134a. Measurements are taken from a test rig at different steady-state conditions: for the cooling mode, the evaporating temperature is −5 °C, −10 °C and −15 °C, and is combined with two condensing temperatures (32.5 °C and 40 °C), and different internal heat exchanger (IHX) effectiveness. Besides, in the heating mode, the evaporating temperature is 7.5, 15 and 22.5 °C with five condensing temperatures (55 °C to 75 °C, step of 5 °C). In the cooling mode, R513A presented the highest system COP amongst the low GWP alternatives, increasing up to 8%. R516A shows the lowest system COP at the highest evaporation temperature; however, it exhibits the highest COP and capacity at the lowest evaporation temperature. The IHX positively influences the refrigerating effect for all adopted refrigerants. Regarding the heating mode, R513A presents the highest heating capacity with an average 3% increase, whereas R516A shows the lowest results. R513A shows comparable COP to R134a, especially at higher evaporating temperatures. [-]
Publicado en
Energy Conversion and Management, Vol. 258, April 2022Entidad financiadora
Southern Technical University, Iraq | MCIN/AEI/10.13039/501100011033