Effect of mean void fraction correlations on a shell-and-tube evaporator dynamic model performance
Ver/ Abrir
Impacto
Scholar |
Otros documentos de la autoría: Navarro-Esbrí, Joaquín; Milián, Víctor; Mota-Babiloni, Adrián; Molés, Francisco; Verdú, Gumersindo
Metadatos
Mostrar el registro completo del ítemcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadatos
Título
Effect of mean void fraction correlations on a shell-and-tube evaporator dynamic model performanceAutoría
Fecha de publicación
2015-08-22Editor
Taylor and FrancisISSN
2374-4731; 2374-474XCita bibliográfica
Joaquín Navarro Esbrí, Víctor Milián, Adrián Mota-Babiloni, Francisco Molés & Gumersindo Verdú (2015) Effect of mean void fraction correlations on a shell-and-tube evaporator dynamic model performance, Science and Technology for the Built Environment, 21:7, 1059-1072, DOI: 10.1080/23744731.2015.1034594Tipo de documento
info:eu-repo/semantics/articleVersión de la editorial
http://tandfonline.com/action/journalInformation?show=aimsScope&journalCode=uhvcVersión
info:eu-repo/semantics/acceptedVersionPalabras clave / Materias
Resumen
In this article, the influence of different mean void fraction correlations on a shell-and-tube evaporator dynamic model performance has been evaluated. The model proposed is based on the moving-boundary approach and ... [+]
In this article, the influence of different mean void fraction correlations on a shell-and-tube evaporator dynamic model performance has been evaluated. The model proposed is based on the moving-boundary approach and includes expansion valve modeling. Several transient tests, using R134a as working fluid, have been carried out varying refrigerant mass flow, inlet enthalpy, and secondary fluid flow. Then model performance, using different mean void fractions, is analyzed from the system model outputs (evaporating pressure, refrigerant outlet temperature, and condensing water outlet temperature). The slip ratio expressions selected are a homogenous and momentum flux model and Zivi, Chisholm, and Smith correlations. The results of the comparison between experimental and model predictions depend on the transient characteristics, and there is not a single slip ratio correlation that provides the best performance in all the cases analyzed [-]
Publicado en
Science and Technology for the Built Environment (2015) 21, 1059–1072Datos relacionados
https://www.tandfonline.com/doi/figure/10.1080/23744731.2015.1034594?scroll=top&needAccess=trueDerechos de acceso
Copyright © 2015 ASHRAE