Experimental influence of an internal heat exchanger (IHX) using R513A and R134a in a vapor compression system
Visualitza/
Impacte
Scholar |
Altres documents de l'autoria: Mota-Babiloni, Adrián; Navarro-Esbrí, Joaquín; Pascual Miralles, Víctor; Barragán Cervera, Angel; Maiorino, Angelo
Metadades
Mostra el registre complet de l'elementcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadades
Títol
Experimental influence of an internal heat exchanger (IHX) using R513A and R134a in a vapor compression systemAutoria
Data de publicació
2019-01-25Editor
ElsevierISSN
1359-4311; 1873-5606Cita bibliogràfica
MOTA-BABILONI, Adrián, et al. Experimental influence of an internal heat exchanger (IHX) using R513A and R134a in a vapor compression system. Applied Thermal Engineering, 2019, vol. 147, p. 482-491Tipus de document
info:eu-repo/semantics/articleVersió de l'editorial
https://www.sciencedirect.com/science/article/pii/S1359431118328382Versió
info:eu-repo/semantics/acceptedVersionParaules clau / Matèries
Resum
Coming refrigeration and air conditioning systems must include low GWP fluids and optimized components. An internal heat exchanger (IHX) is a common modification of the basic cycle to enhance its energy performance, ... [+]
Coming refrigeration and air conditioning systems must include low GWP fluids and optimized components. An internal heat exchanger (IHX) is a common modification of the basic cycle to enhance its energy performance, and its benefits have been demonstrated with R134a and the recently developed hydrofluoro-olefin R1234yf. This paper assesses the experimental influence of a high effectiveness IHX using R134a, and the low GWP mixture R513A (a mixture of R134a and R1234yf) under different evaporating and condensing conditions (29 points tested in total). Discharge temperature has been increased up to 26 K for both fluids, and the greatest compression ratio is not feasible for R134a. The cooling capacity of the system results increased up to 5.6% for R513A whereas for R134a is around 3%. Furthermore, due to the minimum diminution of power consumption, COP also increases up to 8% for R513A and 4% for R134a. Because of the observed experimental results, high effectiveness IHX is recommended for R513A, especially for high compression ratio operations as long as the discharge temperature does not reach critical values. Finally, it has been found that Klein et al.’s and Hermes’s correlations overestimate the COP benefit and the increase in power consumption should be considered. [-]
Publicat a
Applied Thermal Engineering, 2019, vol. 147Proyecto de investigación
Spanish State Research Agency: FJCI-2016-28324; University Jaume I of Spain: E-2017-30Drets d'accés
© Elsevier Ltd. All rights reserved.