Positive-Net-Damping Stability Criterion in Grid-Connected VSC Systems
Visualitza/
Impacte
Scholar |
Altres documents de l'autoria: Sainz, Luis; Cheah-Mane, Marc; Monjo, Lluís; Liang, Jun; Gomis-Bellmunt, Oriol
Metadades
Mostra el registre complet de l'elementcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7034
comunitat-uji-handle3:10234/8619
comunitat-uji-handle4:
INVESTIGACIONMetadades
Títol
Positive-Net-Damping Stability Criterion in Grid-Connected VSC SystemsData de publicació
2017-05Editor
Institute of Electrical and Electronics Engineers (IEEE)Cita bibliogràfica
SAINZ, L., et al. Positive-Net-Damping Stability Criterion in Grid-Connected VSC Systems. IEEE Journal of Emerging and Selected Topics in Power Electronics, 2017.Tipus de document
info:eu-repo/semantics/articleVersió de l'editorial
http://ieeexplore.ieee.org/abstract/document/7933072/Versió
info:eu-repo/semantics/submittedVersionParaules clau / Matèries
Resum
Resonance instabilities in power systems can be assessed with the positive-net-damping stability criterion. This criterion is a review of the complex torque coefficients method but it does not provide the frequency ... [+]
Resonance instabilities in power systems can be assessed with the positive-net-damping stability criterion. This criterion is a review of the complex torque coefficients method but it does not provide the frequency of the closed-loop oscillatory modes. This paper presents an alternative approach of the positive-net-damping stability criterion to analyze electrical resonance instability. In this approach, resonance instabilities are identified in feedback systems derived from impedance-based equivalent circuits. The proposed approach is used to characterize the frequency of closed-loop oscillatory modes and identify the physical and control parameters of the system that increase or reduce the damping of these modes. The extension of the proposed approach to study the stability of Single-Input Single-Output and Multiple-Input Multiple-Output feedback systems is analyzed and the approach is also compared with other stability methods in the literature. An example of an offshore wind power plant illustrates the theoretical study and compares the proposed approach with different methods to evaluate stability. Time-domain simulations in PSCAD/EMTDC are shown to validate the stability study. [-]
Drets d'accés
(c) 2017 IEEE. Personal use of this material is permitted. Permission from IEEE must be obtained for all other users, including reprinting/ republishing this material for advertising or promotional purposes, creating new collective works for resale or redistribution to servers or lists, or reuse of any copyrighted components of this work in other works.