R-407H as drop-in of R-404A. Experimental analysis in a low temperature direct expansion commercial refrigeration system
Ver/ Abrir
Impacto
Scholar |
Otros documentos de la autoría: Llopis, Rodrigo; Sánchez García-Vacas, Daniel; Cabello López, Ramón; Nebot-Andres, Laura; Catalán-Gil, Jesús
Metadatos
Mostrar el registro completo del ítemcomunitat-uji-handle:10234/9
comunitat-uji-handle2:10234/7035
comunitat-uji-handle3:10234/8617
comunitat-uji-handle4:
INVESTIGACIONMetadatos
Título
R-407H as drop-in of R-404A. Experimental analysis in a low temperature direct expansion commercial refrigeration systemAutoría
Fecha de publicación
2017-08Editor
ElsevierCita bibliográfica
LLOPIS, Rodrigo, et al. R-407H as drop-in of R-404A. Experimental analysis in a low temperature direct expansion commercial refrigeration system. International Journal of Refrigeration, Volume 80, August 2017.Tipo de documento
info:eu-repo/semantics/articleVersión de la editorial
http://www.sciencedirect.com/science/article/pii/S0140700717301883Palabras clave / Materias
Resumen
This work analyses experimentally the possibility of using the reduced GWP refrigerant R-407H (HFC family, GWP = 1378) as drop-in substitute of R-404A (HFC family, GWP = 3945) in low temperature centralized direct ... [+]
This work analyses experimentally the possibility of using the reduced GWP refrigerant R-407H (HFC family, GWP = 1378) as drop-in substitute of R-404A (HFC family, GWP = 3945) in low temperature centralized direct expansion refrigeration system. The experimental plant and the test methodology are described. It covered top up or partial drop-in and energy consumption tests at −20 °C of product temperature and 25, 35 and 45 °C of condensing temperature using a small-scale supermarket under laboratory conditions. It has been measured that the use of R-407H instead of R-404A is favourable from the point of view of energy efficiency. Reductions in the energy consumption of up to 7.7% (compressor) and 4.0% (whole system) have been measured. However, there is an increment in the compressor's discharge temperature of up to 13.8 K. In addition, the operation of the system with both refrigerants was correct. [-]
Publicado en
International Journal of Refrigeration Volume 80, August 2017Derechos de acceso
© 2017 Elsevier Ltd and IIR. All rights reserved.